12/20 kV or 12.7/22 kV XLPE insulated double steel tape armoured, three core cables with copper conductor
YXC8VZ4V-R, N2XSEYBY, CU/XLPE/CTS/PVC/STA/PVC
R, Örgülü rijit iletken
Standards
TS IEC 60502, BS 6622, VDE 0276
Technical Data
Max. operating temperature: 90°C
Max. short circuit temperature: 250°C (max. 5 sn.)
Rated voltage: 12/20 kV
: 12.7/22 kV
Min. bending radius: 15 x D
D: Cable outer diameter
Application
These are cables with low dielectric losses used in energy networks with sudden load changes where mechanical stresses expected. Laid in residential or industrial areas, underground or in ducts
Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation.
4. Outer semi-conductive layer.
5. Semi-conductive tape.
6. Copper tape screen.
7. Filler.
8. PVC inner jacket.
9. Galvanized double steel tape.
10. PVC outer jacket.