0.6/1 kV PVC Insulated, Flat Steel Wire Armoured, Multi-Core Cables With Copper Conductor

  • 0.6/1 kV PVC Insulated, Flat Steel Wire Armoured, Multi-Core Cables With Copper Conductor

    Code
    YVZ3V-R, CU/PVC/SWA/PVC, NYFGbY
    R, Stranded conductor

    Standards
    TS IEC 60502 - 1, VDE 0271

    Technical Data
    Max. operating temperature: 70°C
    Max. short circuit temperature: (max. 5 sn)
    Cross section < 300 mm: 160°C
    Cross section > 300 mm: 140°C
    Rated voltage: 0.6/1 kV
    Min. bending radius: 12 x D
    D: Cable outer diameter
        
    Application
    Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

    Construction
    1. Stranded copper conductor.
    2. PVC insulation.
    3. Filler.
    4. Galvanized flat steel wire.
    5. Galvanized steel binding tape.
    6. PVC outer sheath.