0.6/1 kV PVC Insulated, Double Steel Tape Armoured, Multi-Core Cables With Copper Conductor

  • 0.6/1 kV PVC Insulated, Double Steel Tape Armoured, Multi-Core Cables With Copper Conductor

    Code
    YVZ4V-U, YVZ4V-R, CU/PVC/STA/PVC, NYBY
    U, Solid conductor
    R, Stranded conductor

    Standards
    TS IEC 60502, VDE 0271

    Technical Data
    Max. operating temperature: 70°C
    Max. short circuit temperature: (max. 5 sn)
    Cross section < 300 mm: 160°C
    Cross section > 300 mm: 140°C
    Rated voltage: 0.6/1 kV
    Min. bending radius: 15 x D
    D: Cable outer diameter
          
    Application
    Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

    Construction
    1. Solid or stranded copper conductor.
    2. PVC insulation.
    3. Filler.
    4. Galvanized double steel tape armoured.
    5. PVC outer sheath.